Heat pump sizing estimate

Estimate your home's design heating load and the cold-climate heat pump capacity you'd need in your part of Ontario, before you talk to contractors.

Last reviewed November 2, 2026
How we review content

Your details

sq. ft.

Above grade plus a heated or finished basement.

Upgrades already done
m³/year

Heating portion only — subtract ~250 m³ for a gas water heater.

Your estimate

Design heating load

43k BTU/h

≈ 12.6 kW at -19 °C

Equivalent size

3.6 tons

of heating capacity needed at design temperature

Check from gas use

—

add gas use above

Look for a cold-climate heat pump that can still deliver about 43k BTU/h at -19 °C, or one slightly smaller paired with backup heat. Nominal “ton” ratings describe cooling capacity at mild temperatures; heating output at −20 °C is often 60–90% of that, so ask for the manufacturer's capacity table.

This is a screening estimate only. A proper room-by-room load calculation (CSA F280) is required for rebates and good comfort. Read why sizing matters or ask contractors for a load calculation.

Assumptions and method

Design load = whole-home heat-loss coefficient × floor area × (21 °C − design temperature). Coefficients range from about 2.2 W/m²·K for pre-1960 homes to 0.95 for homes built after 2012, reduced 10% for each completed envelope upgrade.

When you enter gas use, the calculator also derives your home's heat-loss rate from actual consumption and regional heating degree days, and weights that estimate two-to-one over the age-based one.

Design temperatures are approximate values for each area under the Ontario Building Code.